24VDC Power Converter
Model Name
STI-PA-24W-24V1A
Introduction
STI-PA-24W-24V1A is a single-phase PSU providing efficient and adjustable DC output.
It could operate in wide temperature range and for industrial automation&control systems etc.
Key Features
- Universal AC Input 90-264V or 127 ~370VDC Input by connecting AC/L(+), AC/N(-)
- DC O/P Voltage Adjustable 21.6V~26.4V
- Protection: Short Circuit/Overload/Over Voltage/Over Temperature
- DC OK Signal Output
- Installation: DIN Rail TS-35/7.5 &15
- CE/RoHS/UKCA/UL Compliant
- 3 years warranty
Specification
Product Name |
24W Din Rail Industrial Power Adapter |
Input |
|
Voltage Range |
90-264VAC, 127 ~370VDC |
Frequency Range |
47~63Hz |
Efficiency(Typ.) |
84% |
AC Current(Typ.) |
0.33A/115VAC 0.21A/230VAC |
Inrush Current(Typ.) |
35A/115VAC cold start 70A/230VAC cold start |
Leakage Current |
<1mA/240VAC |
Output |
|
Power |
24W max. |
Output Voltage |
24V |
Output Current |
1A |
Ripple&Noise(max.) |
150mVp-p |
Voltage Adj. Range |
21.6~26.4V |
Voltage Tolerance |
±2.0% |
Line Regulation |
±1.0% |
Load Regulation |
±5.0% |
Setup, Rise Time |
500ms, 30ms/230VAC at full load 1000ms, 30ms/115VAC at full load |
Hold Up Time(Typ.) |
50ms/230VAC at full load 20ms/115VAC at full load |
Protection |
|
Over Load |
105~150% rated output power Protection type: Hiccup Mode- recovers automatically after fault condition is removed |
Over Voltage |
27.6~32.4V, Shut down o/p voltage, re-power on to recover |
Environment |
|
Working Temp. |
-20℃ ~ +70℃(Refer to"Derating Curve") |
Working Humidity |
20~95% RH non-condensing |
Storage Temp. |
-40℃ ~ +85℃, 10~95% RH |
Storage Humidity |
20~90% RH |
MTBF |
2363.7K hrs min. Telcordia SR-332(Bellcore) |
Note
- All parameters NOT specially mentioned at 230VAC input, rated load and 25℃ of ambient temperature.
- Ripple&noise are measured from peak to peak with band width limit of 20MHZ(0.1uF and 47uF/50V parallel capacitor under DC output full load,AC nominal input 25℃ ambient temperature).
- Installation clearances: top with 40mm, bottom with 20mm, left and right with 5mm. Increase the space to 10-15mm when the adjacent device is heat source.
- Derating may be needed under low input voltage. Please check the derating curve for more details.
- Efficiency test after 30 minutes of burn-in.
- The ambient temperature derating of 3.5℃/1000m for operating altitude higher than 2000m(6500ft).
Safety&EMC |
|
Safety Standards |
UL508, UL1310, BS/EN62368-1 approved |
Withstand Voltage |
I/P-O/P: 3KVAC I/P-FG: 2KVAC O/P-FG: 0.5KVAC |
Isolation Resistance |
I/P-O/P, I/P-FG, O/P-FG: >100M Ohms/500VDC/25℃/70% RH |
EMC Emission |
BS EN/EN 55032 class B, BS EN/EN EC 61000-3-2, -3 |
EMC Immunity |
BS EN/EN61000-4-2, 3, 4, 5, 6, 8, 11 |
Dimension&Weight |
|
Width |
23mm/0.91in |
Height |
100mm/3.94in |
Depth |
92mm/3.62in |
Weight |
0.15KG |
Packing |
|
Carton Size |
54*30*24cm 21.26*11.81*9.45in |
Master Carton Quantities |
100pcs/Carton |
Functional Diagram
Dimension
Deduction Curve and Temperature
Minus Output and input Voltage Curves